Features
- Designed to operate with entering water temperatures between 25° F and 100°F
- High efficiency scroll compressors with crankcase heaters
- Cabinet constructed of G-90 galvanized steel and finished with electro deposition
acrylic paint
- Stainless steel exterior hardware
- Coaxial heat exchanger, refrigerant lines and water lines fully insulated
- Blower is double inlet, double wide, constructed of galvanized steel
- Fan motor contains sealed bearings and does not require lubrication
- Indoor air coil is aluminum plate-finned with seamless copper
- Compressor control module sequences components at start-up
- High and low pressure safety controls
- Options include: auxiliary heat, economizer, motorized damper, matching roof curb,
seacoast construction
- Horizontal and downflow
| Model |
Water Loop Application |
Group Loop Application |
Btuh Cooling
|
EER |
Btuh Heating |
COP |
Btuh Cooling |
EER |
Btuh Heating |
COP |
| 036 |
34,500 |
14.1 |
42,900 |
4.4 |
35,800 |
14.9 |
24,100 |
3.5 |
| 048 | 49,600 |
13.0 |
59,600 |
4.5 |
52,000 |
14.9 |
35,000 |
3.5 |
| 060 | 60,600 |
12.8 |
73,000 |
4.6 |
60,200 |
14.1 |
47000 |
3.2 |
| 072 |
75,200 |
12.8 |
83,300 |
4.6 |
76,300 |
15.9 |
55400 |
3.7 |
| 096 |
95,000 |
12.5 |
113,000 |
4.2 |
96,000 |
13.5 |
71400 |
3.2 |
| 120 |
119,000 |
12.0 |
140,000 |
4.0 |
120,000 |
13.4 |
93100 |
3.2 |
| 150 |
150,700 |
12.5 |
185,000 |
4.3 |
154,000 |
13.6 |
120500 |
3.2 |
| 180 |
171,900 |
13.9 |
208,000 |
4.6 |
178,200 |
15.7 |
133600 |
3.5 |
| 240 |
229,800 |
12.5 |
287,100 |
4.3 |
236,900 |
14.5 |
180600 |
3.4 |
| 300 |
276,400 |
13.6 |
343,100 |
4.6 |
285,000 |
14.8 |
230000 |
3.6 |
| 360 |
376,500 |
12.4 |
459,100 |
4.2 |
383,100 |
14.0 |
304100 |
3.2 |
| 420 |
426,700 |
12.1 |
550,000 |
4.2 |
440,000 |
13.4 |
369000 |
3.2 |
Rated in accordance with ISO Standard 13256-1
|